QTY |
FOB PRICE |
CIF PRICE
QUANTITY
-
+
SET
TOTAL COST
$1660Material : Default |
Pcs/Carton : N/A | Packing Size/Carton : N/A | Packing Vol/Carton : N/A |
N.W./Carton : N/A | G.W./Carton : N/A | QTY in 40HQ : N/A |
QTY in 40GP : N/A | QTY in 20GP : N/A |
The Castle Series C UPS 1kVA~3kVA(S)
Product performance
The Castle series On-line UPS is an advanced true double conversion On-line Topology, the Castle Isolated gate Bipolar Transistors (IGBT) for true isolation from AC input. Ideal for Data Centers in network and Industrial applications.
Technical parameters
The Castle series On-line UPS is an advanced true double conversion On-line Topology, the Castle Isolated gate Bipolar Transistors (IGBT) for true isolation from AC input. Ideal for Data Centers in network and Industrial applications. Features scalable battery packs for those critical business systems that require long run times. With the Castle wide in-put voltage range and near zero tolerance on frequency and voltage variance on the put-put the Castle series is perfect for the most demanding and delicate of applications.
Sine-wave output:
True sine-wave output with less than 3% THD.
Double Conversion Design:
Zero transfer/ complete isolation of input AC.
UPS Monitoring Software:
Powerful true RS232 communication via the enclosed software
to manage and safely shutdown operating systems.
Network RJ45/11 protection:
Complete powerful network and phone line surge protection.
AC Surge Suppressor:
Powerful multi-stage surge components that exceed IEEE requirements.
SNMP Slot Option:
Allows for remote monitoring and control via www.
Sleep Mode:
Worry free battery management. The unit turns itself off after ten seconds to conserve battery
power when no power needs are detected.
Battery level indicators:
LED''s indicate battery levels.
Load Sensing:
The incorporated LED load indicators allow IT professionals to manage backup time and balance
power loads.
Low Battery indicators:
The low battery level indicator will warn of eminent UPS shutdown two full minutes before unit shuts
down.
Replace Battery indicators:
A preventative measure that indicates when batteries must be replaced to prevent
server crashes.
TECHNICAL SPECIFICATIONS:
Product Series |
CASTLE |
|||
Model |
C1K |
C2K |
C3K |
|
Rated Power |
VA/W |
1kVA / 0.7kW |
2kVA / 1.4kW |
3kVA / 2.1kW |
Input |
Nominal Voltage |
220VAC |
||
Voltage Range |
115 ~ 300VAC |
|||
Frequency Range |
46~54Hz(default), user adjustable within 40~60Hz |
|||
Power Factor |
0.97 |
|||
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
||
Output |
Voltage |
220VAC ± 2% |
||
Frequency |
46~54Hz or 50Hz ± 0.2Hz (Line mode) |
|||
Waveform |
Sine Wave |
|||
Distortion |
3% |
4% |
||
Overload Capability |
108%~150% for 30 sec., ³150% for 300 ms |
|||
Current Crest Ratio |
3:1 |
|||
Connections |
IEC320 * 4 |
IEC320 * 6 |
IEC320 * 3 and |
|
Battery |
Type |
Sealed, Maintenance free, Lead-Acid |
||
Quantity |
3 pieces |
8 pieces |
||
Back-up Time (Full load) |
5 min |
9 min |
5 min |
|
Recharge Time |
5 hrs to 90% of capacity after full load discharge |
|||
Bypass |
Automatic Transfer |
on overload and UPS failure |
||
Before UPS Power-on |
Default “NO”, user adjustable to “YES” |
|||
Voltage Range |
80~264VAC (Default), user adjustable within 80~286VAC |
|||
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and vice versa |
|||
LED Indicators |
Status |
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault |
||
Audible Alarm |
Bypass, On battery mode, Battery low, Overload, Fault |
|||
Acoustic Noise |
At 1 meter distance |
45 dBA |
50 dBA |
|
Communications |
DB-9 Port |
RS-232 Serial Interface |
||
Intelligent Slot |
Options: Web Power, AS400 Card or Win Power CMC |
|||
Network Surge Protection |
RJ45 I/O port available for network or Fax/Modem |
|||
Environmental |
Operating Temperature |
0 ~ 40°C |
||
Operating Humidity |
20 ~ 90% non-condensing |
|||
Weight |
Net (Kg) |
13 |
31.5 |
32 |
Dimensions |
W x D x H (mm) |
145 x 400 x 220 |
192 x 460 x 348 |
Model |
C1KS |
C2KS |
C3KS |
|
Rated Power |
VA/W |
1kVA / 0.7kW |
2kVA / 1.4kW |
3kVA / 2.1kW |
Input |
Nominal Voltage |
220VAC |
||
Voltage Range |
115 ~ 300VAC |
|||
Frequency Range |
46 ~ 54Hz(default), user adjustable within 40~60Hz |
|||
Power Factor |
0.97 |
|||
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
||
Output |
Voltage |
220VAC ± 2% |
||
Frequency |
46~54Hz or 50Hz ± 0.2Hz (Line mode) |
|||
Waveform |
Sine Wave |
|||
Distortion |
3% |
4% |
||
Overload Capability |
108% ~ 150% for 30 sec., ³150% for 300 ms |
|||
Current Crest Ratio |
3:1 |
|||
Connections |
IEC320-10A *4 |
IEC320-10A *6 |
IEC320-10A *3 and |
|
Battery |
Type |
Sealed, Maintenance free, Lead-Acid |
||
Nominal DC Voltage |
36VDC |
96VDC |
||
Back-up Time |
Depends on the capacity of the external battery bank |
|||
Connection |
External Battery Socket |
|||
Bypass |
Automatic Transfer |
On overload and UPS failure |
||
Before UPS Power-on |
Default “NO”, user adjustable to “YES” |
|||
Voltage Range |
80 ~ 264VAC (Default), user adjustable within 80 ~ 286VAC |
|||
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and vice versa |
|||
LED Indicators |
Status |
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault |
||
Audible Alarm |
Bypass, On battery mode, Battery low, Overload, Fault |
|||
Acoustic Noise |
At 1 meter distance |
45 dBA |
50 dBA |
|
Communications |
DB-9 Port |
RS-232 Serial Interface |
||
Intelligent Slot |
Options: WebPower, AS400 Card or WinPower CMC |
|||
Network Surge Protection |
RJ45 I/O port available for 10 base-T network or Fax/Modem |
|||
Environmental |
Operating Temperature |
0 ~ 40°C |
||
Operating Humidity |
20 ~ 90% non-condensing |
|||
Weight |
Net (Kg) |
7 |
13.5 |
14 |
Dimensions |
W x D x H (mm) |
145 x 400 x 220 |
192 x 460 x 348 |
• Amanbo Return Policy applies to all orders on amanbo.com.
• If products are not as described, returns are accepted and return shipping fee should be paid by buyer.
• If products are as described, seller has the right to refuse return. Buyer should pay return shipping fee if return require is insisted on.